CoEpo-APF Series Active Power Filter (Rack-Mounted)
Contact Info
- Add:高新区纬二十六路中交科技城西区9号楼, Zip: 710000
- Contact: 陈先生
- Tel:18192712620
- Email:chenxin@coepower.com
Other Products
The CoEpo-APF series active power filter is connected in parallel to the power system. Through external sampling circuits, it collects real-time power system data. The device's internal core computing chip analyzes the harmonic component data in the system and controls the high-frequency switching of IGBT to output a current that is equal in magnitude and opposite in direction to the harmonic current in the system, thereby canceling out the harmonic current in the system to achieve the goal of managing harmonic currents.
| APF Active Filter Specifications | ||||||
| Voltage Level | 0.4KV/0.48KV/0.69KV | |||||
| Current Level | 50A | 75A | 100A | 150A | 200A | Stackable Capacity |
| System Parameters | ||||||
| Rated Input Voltage | 304Vac-456Vac/288Vac-576Vac/414Vac-759Vac | |||||
| Grid Frequency | 50Hz (Range: 45Hz-55Hz), 60Hz (Range: 55Hz-65Hz) | |||||
| Reactive Power Compensation | Capable of reactive power compensation, compensation range (1 ~ -1) | |||||
| Three-Phase Unbalance Regulation | Capable of three-phase unbalance regulation | |||||
| Protection Functions | Grid overload, undervoltage, phase loss, three-phase instantaneous overcurrent, three-phase delayed overcurrent, Bus overvoltage, bus undervoltage, overheating, fan failure, power supply failure, current limiting protection, frequency protection, fuse failure | |||||
| Grid Structure | Three-Phase Four-Wire | Three-Phase Three-Wire | ||||
| Performance Indicators | ||||||
| Filtering Range | 2nd to 50th order | |||||
| Switching Frequency | 20KHz | |||||
| Filtering Capability | THDi < 5% (rated load, THDu < 1%) | |||||
| Fast Response Time | < 40μs | |||||
| Full Response Time | < 10ms | |||||
| Target PF | -1 ~ +1 | |||||
| Communication and Monitoring | ||||||
| Communication Interface | RS485, Ethernet port | |||||
| Communication Protocol | Modbus protocol, Transmission Control Protocol/Internet Protocol | |||||
| Module Display Interface | 4.3-inch touch screen 7-inch LCD touch screen | 7-inch LCD touch screen | ||||
| Installation Method | Wall-mounted/Rack-mounted | Cabinet-mounted | ||||
| Wiring Method | Top entry/Rear entry | |||||
| Centralized Monitoring | Optional 10In centralized monitoring touch screen, each centralized monitoring touch screen can manage up to 6 APF modules | |||||
| Width*Depth*Height (mm) | 540x545x190/540x551x219 | 600x800x2000 | ||||
| CT Wiring Method | Supports source side/load side | |||||
| Environmental Requirements | ||||||
| Operating Temperature | -10℃ ~ +45℃ | |||||
| Relative Humidity | 5% ~ 95%, non-condensing | |||||
| Protection Level | IP20 | |||||
| Cooling Method | Intelligent air cooling | |||||
| Altitude | 2000m, derating required for higher altitudes | |||||
Product Features
1. Capable of harmonic management, reactive power compensation, and three-phase unbalance management. The priority of functions can be flexibly adjusted according to on-site requirements.
2. Full response time of 10ms, enabling the system to maintain an ideal state with THDI less than 5%, PF reaching 0.99, and three-phase unbalance less than or equal to 3%.
3. Can filter 2nd to 50th order harmonics. Within this range, harmonic orders can be arbitrarily selected, and the filtering output can be adjusted to achieve the desired filtering effect.
4. Reactive power compensation range (-1 ~ 1), capable of switching between capacitive and inductive reactive power to meet the compensation needs of equipment with rapidly changing reactive power, such as stamping and welding machines.
5. Modular design for easy maintenance and installation. Supports both rack-mounted and wall-mounted installation methods.
6. Independent air duct design ensures excellent heat dissipation capability. Equipped with a comprehensive temperature detection system to monitor device temperature in real time.
7. Comprehensive protection functions with 16 types of protection to ensure device and system safety.
| APF Selection Reference Table (Reference Values) | |||||
| Commercial Real Estate/Subway | Medical/Metallurgy | Data Centers | Multimedia | Petrochemical/Heavy Industry | |
| Transformer (KVA) | 15% | 20% | 25% | 30% | 35% |
| Recommended Configuration Capacity (A) | |||||
| 200 | 50 | 50 | 50 | 75 | 100 |
| 250 | 50 | 50 | 75 | 75 | 100 |
| 315 | 50 | 75 | 100 | 100 | 125 |
| 400 | 50 | 75 | 100 | 125 | 150 |
| 500 | 75 | 100 | 125 | 150 | 200 |
| 630 | 100 | 125 | 175 | 200 | 250 |
| 800 | 100 | 150 | 200 | 250 | 300 |
| 1000 | 150 | 200 | 250 | 300 | 350 |
| 1250 | 175 | 250 | 300 | 400 | 450 |
| 1600 | 200 | 300 | 400 | 500 | 550 |
| 2000 | 250 | 375 | 500 | 600 | 700 |
| 2500 | 300 | 450 | 600 | 700 | 850 |
| All the above data are empirical values of harmonic distortion under normal operating conditions of the transformer. | |||||
Application Areas
1: Power systems in areas with high grid harmonics, such as factories and enterprises.
2: Production enterprises using high-power nonlinear loads and impact loads (e.g., air pumps).
3: Power systems with high requirements for grid quality, such as hospitals.
4: Power systems requiring comprehensive compensation for reactive power, harmonics, and three-phase unbalance.
5: Sites for retrofitting existing equipment or requiring installation alongside switchgear cabinets.